KYN28/-/12(GZS1)Type Medium/-mounted Switchgear

GZS1 type metal-clad draw-out AC enclosed switchgear(also known as medium-mounted switchgear)is an indoor complete power distribution device

Category:

High Voltage Switchgear


Phone

Service Phone:

Product Description

1. Overview

GZS1 type metal-clad draw-out AC enclosed switchgear(also known as medium-mounted switchgear)is an indoor complete power distribution device,which is used to receive and distribute electric energy of 3.6~12 kV,and has the functions of controlling,protecting and detecting the circuit.

2. Product Features

● The cabinet shell has a high degree of sealing,with strong anti-corrosion and anti-oxidation capabilities.The protection level of the outer shell is IP4X.

● The circuit breaker adopts a medium-mounted operation mode,and VS1 or VD4 vacuum circuit breakers are optional.

● The product is equipped with a perfect mechanical anti-misoperation interlocking device and has the ability to resist internal arc accidents,ensuring the safety of operators in case of accidents.

● The product complies with GB39063~35KVAC Metal-Enclosed Switchgear.

3. Model Composition Meaning

4. Operating Environmental Conditions

Normal service conditions

a.Ambient air temperature:Upper limit:+40℃;Lower limit:-10℃;

b.Altitude:1000m;

c.Relative ambient humidity:Daily average not more than 95%,monthly average not more than 90%;

d.Seismic resistance:Earthquake intensity not exceeding 8 degrees;

e.Ambient air should not be significantly polluted by corrosive or flammable gases,water vapor,etc.;

f.No severe pollution or frequent severe vibrations.Under harsh conditions,the severity design meets the requirements of Class I.

Special service conditions

When used under normal environmental conditions exceeding those specified in GB3906,it can be negotiated between the user and our company.

5. Technical Parameters

Item

Unit

Data

Rated Voltage

kV

3.6 7.2 12

Rated Current

A

630 1250 1600 2000 2500 3150

Rated Frequency

Hz

50

Rated Short-time Withstand Current

kA

31.5

Rated Peak Withstand Current

kA

80

Rated Power Frequency Withstand Voltage

Phase-to-phase, phase-to-ground

kV

42/1min

Across the break

kV

48/1min

Rated Lightning Impulse Withstand Voltage

Phase-to-phase, phase-to-ground

kV

75

Across the break

kV

85

Rated Short-circuit Duration

s

4

Protection Level

 

IP4X

6. Dimensions and Weight

Height A (mm): 2300

Width B (mm): 800/1000

Depth (mm): 1500 for cable, 1660 for overhead

Weight (Kg): 800~1200