HXGN15-12 Type Ring Main Unit

Suitable for use in power distribution systems in industrial and mining enterprises, residential communities, high-rise buildings, and other places for receiving and distributing electrical energy.

Category:

High Voltage Switchgear


Phone

Service Phone:

Product Description

1. Overview

The HXGN15-12 type ring main unit is an indoor metal fully enclosed ring main switchgear for AC three-phase 10kV, 50Hz. It is suitable for use in distribution systems of industrial and mining enterprises, residential communities, high-rise buildings, and other places for receiving and distributing electrical energy. The load switch fuse combination device can interrupt the rated short-circuit current in one operation. The typical combination of the ring main unit generally consists of three basic units, assumed as units A, B, and C. Units A and C are cable incoming and outgoing units respectively, and unit B connects to the transformer, serving protection and isolation functions to facilitate maintenance and repair. When a fault occurs on any line in units A or C, it can be isolated promptly, and the other unit ensures continuous power supply to unit B.

2. Product Features

● The ring main unit can be extended arbitrarily and can implement dual power supply.

● The ring main unit implements electromagnetic interlocking to ensure operational safety.

● The ring main unit can flexibly be equipped with CT and PT to achieve high supply and high metering.

● The ring main unit is equipped with a manual operating lever for manual operation and can be optionally equipped with an electric operating mechanism. The combination electrical cabinet can be used independently as a control device for electrical energy in 10kV, 50Hz power systems.

● The product complies with GB3906 "3~35kV AC Metal-Enclosed Switchgear", GB16926, GB3804, and IEC298 standards.

3. Model Composition Meaning

4. Technical Parameters

Item
Unit
Parameter
Rated Voltage
kV
12
Rated Frequency
Hz
50
Rated Current
A
630
Rated Lightning Impulse Withstand Voltage
Phase to Phase, Phase to Ground
kV
75
Across the Break
kV
85
One Minute Power Frequency Withstand Voltage
Phase to Phase, Phase to Ground
kV
42
Across the Break
kV
48
Rated Short-Time Withstand Current
Main Circuit
kA
20/25
Grounding Circuit
kA
20/25
Rated Short-Circuit Duration
s
3/2
Rated Peak Withstand Current
kA
50
Transfer Current
A
1300/3150
Protection Level
 
IP3X
Load Switch Mechanical Life
Times
3000~20000
Grounding Switch Mechanical Life
Times
1000

5. Overall Dimensions

Standard Cabinet: 900 (W) × 900 (D) × 2000 (H)